FULLTEST 3
EN - 55
5.12. LEAKAGE CURRENT (ILEAK)
5.12.1. LEAKAGE DISPLAY EXPLANATION
Adjustable/selectable parameters:
MODE - measurement mode CLAMP or SOCKET
LIMIT - leakage current limit value 0.1 100.0 mA, 101 1000 mA (CLAMP mode, range 1000 mA)
0.1 100.0 A (CLAMP mode, range 100.0 A)
1 1000 A (CLAMP mode, range 1000 A)
0.01 19.99 mA, 20.0 49.9 mA, 0.05 0.99 A, 1.0 10.0 A
(SOCKET mode)
RANGE - clamp measurement range 1000 mA, 100.0 A or 1000 A
L POS - phase position LEFT or RIGHT
Figure 42: Display with ILEAK test result in CLAMP mode
1 ..... Selected function.
2 ..... Measurement screen touch-screen key.
3 ..... MODE touch-screen key to select measurement mode (SOCKET or CLAMP). Currently selected
mode is displayed on the bottom of the key.
4 ..... RANGE touch-screen key to select the CLAMP measurement range. Currently selected range is
displayed on the bottom of the key.
5 ..... LIMIT touch-screen key to select limit leakage current. Currently selected value is displayed on the
bottom of the key.
6 ..... Measurement result (in green colour - result OK, in red colour - result not OK).
7 ..... Real time clock (hh.mm.ss).
8 ..... Unit of the test result.
9 ..... Measurement result status (symbol in green colour - result OK, symbol in red colour - result
not OK).