FULLTEST 3
EN - 87
PHASE SEQUENCE (PHASESEQ)
Display range
UL1/2, UL2/3, UL3/1
(V)
Resolution
(V)
Accuracy Overvoltage protection
360 460
1 ± (2% rdg. + 2 dgt) CAT III 300 V
Display of test result: 1.2.3 (right) or 2.1.3 (left) or 1.1.X (not defined)
TRMS Clamp Current (ICLAMP)
Range Display range Resolution
Accuracy
(w/o clamp error)
Overvoltage protection
1000 mA
0.0 99.9 mA
0.1 mA
± (3% rdg. + 3 dgt)
One measurement
terminal grounded
100 1000 mA
1 mA
100.0 A
0.00 9.99 A
0.01 A
10.0 100.0 A
0.1 A
1000 A
0.0 99.9 A
0.1 A
100 1000 A
1 A
Input voltage range: 0 1 V AC
Input resistance: 1 M
Frequency range: 40 Hz 100 kHz (characteristics according to
DIN EN 61010-1 Annex A, fig. A.1 and VDE 0411 Part 1)
Clamp type: AC, output voltage 1 V / measuring range, type
HT96U (measuring ranges 1 A, 100 A, 1000 A)
LIM value (1000 mA range): Adjustable 0.1 ... 99.9 mA, 100 ... 1000 mA
LIM value (100.0 A range): Adjustable 0.1 ... 100.0 A
LIM value (1000 A range): Adjustable 1 ... 1000 A