Ht-instruments PQA824 Manual de usuario Pagina 103

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 102
PQA400 - PQA823 - PQA824
EN - 102
5.5.2.4. Vectors
This screen (Fig. 167) displays, with graphic and numeric indications, the phase delays
expressed in degrees [°] between:
Voltage V1 and V2, V2 and V3, V3 and V1.
Voltage V1 and current I1.
Voltage V2 and current I2.
Voltage V3 and current I3.
The latter allow finding out the inductive or capacitive nature of the electrical installation. In
detail:
Positive angle: Inductive load.
Negative angle: Capacitive load.
The N-PE voltage (blue) and Neutral current (pale blue - not for PQA400) vectors are also
represented.
Fig. 167: Total vector diagram in three-phase 4-wire system
The following keys are active on this page:
The F1 key (or the PAG item on the display) advances to the following page of
saved values relative to the voltage vector diagram.
The ESC key (or the smart icon on the display) to exit the function and go back
to the “Recording analysis” page (Fig. 143).