4.2.2. Special cases which may occur during the tests "MAN", "AUTO", "TIMER"
In case a value of R
ISO
higher than
R
MAX
was detected (depending on the
selected voltage see following Note
table, the instrument emits a double
sound signal at the end of the test
indicating the positive outcome of the
test and displays one screen similar to
the screen alongside.
R
ISO

> 999 M
500 V 20 s
MAN
In case a test is effected at a voltage
lower than the set rated voltage, at
the end of the test the instrument emits
a long sound signal and displays one
screen similar to the screen alongside.
R
ISO

0.01 M
500 V 20 s
MAN
SAVING: The test can be stored pressing the SAVE key twice
(according to § 5.1).
If the terminal voltage is higher than
30V, the instrument does not effect the
test, displays the screen alongside for 5
seconds after which, it shows the
default screen relative to the R
ISO
test
under selected mode.
R
ISO

33V
VOL AG
THIS RESULTS CANNOT BE SAVED.
ATTENTION: the
test was not
carried out.
Check that the
circuit is not
energised.
The symbol ">"
means that the
resistance value
R
ISO
is higher than
R
MAX
Test duration
Selected mode
MAN
Selected mode
MAN
ATTENTION: the test of resistance R
ISO
was
effected at a voltage value lower than the set
rated voltage. Low insulation case. This case
occurs under low insulation conditions or in the
p
resence of ca
p
acit
y
on the installation.
Maximum resistance value which can be
measured (999 is displayed if a rated voltage of
500V was selected see table).
SAVE
SAVE