NOTE: ”Man 5 I
∆n
” and “AUTO” test modes aren’t available for RCD type A 500mA.
At the end of the test if
all six tests resulted to
be positive, the
instrument displays the
screen alongside
relative to the last
measurement effected.
RCD ~
23 ms
OK
Ι
∆N
30mA 1 V
x5
t
AUTO 180° U
L
= 50V
5. Press the DISP key to scroll the results relative to the six tests
effected which can be shown cyclically according to the following
order: ½I
∆n
at 0°, ½I
∆n
at 180°, I
∆n
at 0°, I
∆n
at 180°, 5I
∆n
at 0°, 5I
∆n
at
180°.
SAVING: The test can be stored pressing the SAVE key twice
(according to paragraph 5.1).
4.3.1.4. Mode "RAMP "
4. Press the START/STOP key once. The instrument carries out the
test injecting a current in phase with positive half wave of the
voltage indicated on display by 0°.
Press the START/STOP key once. The instrument carries out the
test injecting a current in phase with negative half wave of the
voltage indicated on display by 180°.
The instrument generates a leakage current growing step by step
for a given time interval.
At the end of the test if the RCD tripping
current is ≤ I
∆n
(Type AC) or 1.4I
∆n
(Type
A with I
∆n
> 10mA) or 2I
∆n
(Type A with
I
∆n
≤ 10mA), the instrument emits a
double sound signal indicating the
positive outcome of the test and
displays the screen alongside.
RCD ~
24 mA
OK
41 ms 1 V
t
0° U
L
= 50 V
SAVING: The test can be stored pressing the SAVE key twice
(according to paragraph 5.1).
OK: indicates that the RCD
passed the test.
Value of contact
voltage U
t
detected referred
to the rated value
of the RCD
current set.
SAVE
SAVE
or RCD
RCD tripping time
OK: indicates that
the RCD passed
the test.
Value of contact voltage U
t
detected referred to the
rated value of the RCD current set.
or RCD
START
STOP
DISP