HT9022
EN - 20
WARNING
If the frequency of the measured voltage is lower than 40Hz or higher than
70Hz, the display shows the message “F<40 Hz” or “F>70 Hz” and phase
detection does not start.
3. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L1 phase cable.
Mod Go
Ph Seq
PH1
Meas
19/01-17:00:00
4. Once phase L1 acquisition is complete, the displays shows
the screen here to the side. Disconnect the test lead from
phase L1 cable.
Mod Go
Ph Seq
Discon.
Wait
19/01-17:00:00
5. The instrument shows the screen here to the side, and waits
for the detection of phase L2.
Connect the test lead to phase L2 cable.
Mod Go
Ph Seq
PH2
Wait
19/01-17:00:00
WARNING
If more than 3 seconds elapse before detecting phase L2, the instrument
displays the message “Time Out”.
It is necessary to repeat the measuring cycle from the beginning, by
pressing key F4 (Go) and starting from step 1 again.
6. When a voltage higher than or equal to 100V is detected, the
instrument gives an acoustic signal (buzzer) and the
message “Meas” is shown on the display. Do not press any
key and keep the test lead connected to L2 phase cable.
Mod Go
Ph Seq
PH2
Meas
19/01-17:00:00